logo

GEA Blu-Red Fusion – High-efficiency cooling and heating in one

The GEA Blu-Red Fusion combines high-performance cooling and heating in a single system. It integrates GEA Blu chillers (low stage) with GEA Red heat pumps (high stage), delivering extended capacity and temperature ranges for demanding industrial applications. CE-certified and equipped with advanced compressor models, it supports energy-efficient, future-ready operations.

Designed for applications with large temperature lifts, Blu-Red Fusion achieves best-in-class efficiency – especially where single-stage systems fall short. Typical uses include food, dairy, and beverage processing (e.g., hot water washdowns, pasteurization), as well as heating-only applications such as district or facility heating using low-grade heat sources like environmental water or wastewater. The system is based on GEA’s proven Blu and Red platforms and can be configured as a single unit for seamless integration.

Optimized for efficiency and sustainability

A high-efficiency ammonia-to-ammonia cascade heat exchanger connects the low and high stages without an intermediate liquid circuit. This minimizes pressure drop, system footprint, and refrigerant charge while reducing energy use and CO₂ emissions by double-digit percentages.

Operating modes for full flexibility
  • Simultaneous cooling and heating (full or part load)
  • Cooling only when no heating is required
  • Heating regulation independent of cooling demand
  • Option to be sized for lower, constant heating demand, avoiding oversizing and reducing overall costs
Talk to an expert
arrow

Key features and highlights

  • Combined cooling and heating using ammonia (R717)
  • Low energy consumption and reduced emissions
  • Wide capacity range: cooling 205–1,810 kW; heating 275–2,400 kW
  • Hot water up to 95 °C; cooling from –15 °C to +15 °C
  • Stepless capacity control (VSD, slide valve, cylinder cut-off)
  • Fully welded shell-and-plate heat exchanger
  • Multiple plate material options for media compatibility
  • Smart control with GEA Omni
Key features and highlights

Technical data - GEA Blu-Red® Fusion

Type¹Heat carrier (°C) in/outHeat carrier (°F) in/outCooling capacity (kW)²Heating capacity (kW)²COP combined³
BG300-RG3540/70104 / 1582052756.40
BG300-RG4540/70104 / 1582603506.35
BG450-RG5540/70104 / 1583354506.38
BG450-RG6540/70104 / 1584305756.44
BG450-RG30040/70104 / 1584806256.86
BG600-RG45040/70104 / 1586708756.84
BG900-RG45040/70104 / 15884011006.78
BG1200-RG60040/70104 / 158127516706.80
BG1400-RG75040/70104 / 158147019506.56
BG1800-RG95040/70104 / 158181024006.61
BA400-RAEC70/80158 / 1762554503.33
BA500-RAED70/80158 / 1763506003.52
BA800-RAHE70/80158 / 1764658003.44
BA900-RAHG70/80158 / 1765659503.59
BA1000-RAMH70/80158 / 17674512503.58
BA1500-RAML70/80158 / 17687014503.67
BA1800-RARM70/80158 / 176109018003.73
BG450-RG35070/95158 / 2033405004.80
BG600-RG35070/95158 / 2035107504.86
BG900-RG35070/95158 / 20368010004.86
BG1200-RG55070/95158 / 203112516504.86
BG1400-RG75070/95158 / 203142021004.80
BG1800-RG95070/95158 / 203169525004.82

¹ BG = BluGenium, BA = BluAstrum, RG = RedGenium, RA = RedAstrum. BG/BA letters refer to compressor housing; RG/RA letters refer to model size and swept volume, ² BG/RG reciprocating compressor speed max. 1500 rpm; BA screw compressor speed max. 4500 rpm; RA screw compressor speed max. 3600 rpm (RM, RN, RR types limited to 3300 rpm), ³ COP combined = cooling plus heating capacity / power consumption at net